Command-signal cables

LIhCH FE 180/E90

Application

Used in electronic control systems at voice frequency, in signal and data transfer, in office devices and measuring devices as the connecting cable.
Most often used for hotels, shopping centers, smart buildings.
Due to their special construction, these halogen-free, fire resistant cables preserve the insulation integrity for 180 minutes.

Technical Characteristics

1. Conductor: fine wire copper conductor, class 5, according to DIN VDE 0295, IEC 60228
2. Insulation: silicon, color coded according to DIN 47100, EN50363-5-E18
3. Separator: polyester foil 100%, glass tape
4. Screen: tinned copper braid wire
5. Sheath: HFFR, RAL 2004 orange EN 50290-2-27

Test

1. Non corrosive combustion gasses test: EN 60754-2
2. Low smoke density test: EN 61034-2
3. Fire resistance and flame retardant test: EN 60332-1-2
4. Insulation integrity test: IEC 60331-21 Fe180
5. Installation functionality during fire test: DIN4102-12-2000
6. Standard: VDE 0815